绝缘操作杆使用注意事项总结
添加时间:2017/4/26 17:18:13     浏览次数:

(1)绝缘操作杆使用前应检查型号规格、制造厂名、制造日期、电压等级及带电作业用(双三角)符号等标识是否清晰完整。

Insulation lever (1) before the use should check specifications, factory name, date of manufacture, voltage grade and charged with the (double triangle) symbols such as identification clear whether complete.

(2)绝缘操作杆应光滑。

(2) insulation lever should be smooth.

(3)绝缘操作杆绝缘部分应无气泡、皱纹、裂纹、绝缘层脱落、严重的机械或电灼伤痕,玻璃纤维布与树脂间应粘结完好不得开胶。

(3) insulation operating rod insulation should be no bubble, wrinkle, crack, insulation layer falls off, severe mechanical or electric bright scar, glass fiber cloth and resin should be in good condition does not glue.

(4)握手的手持部分护套与操作杆应连接紧密、无破损,不产生相对滑动或转动。

(4) shake hands holding a part of the sheath and lever should be compact connection, without damage, do not produce the relative sliding or rotating.

(5)绝缘操作杆的规格必须符合被操作设备的电压等级,切不可任意取用。

(5) of the specifications of the insulation lever must comply with the operating equipment voltage grade, must not.

(6)操作前,绝缘操作杆表面应用清洁的干布擦试干净,使表面干燥、清洁。

(6) before operation, insulation operating rod surface application of clean dry cloth to wipe clean, make the surface dry and clean.

(7)操作时,人体应与带电设备保持足够的安全距离。

(7), the body should keep enough safety distance with electric equipment.

(8)操作者的手握部位不得越过护环,以保持有效的绝缘长度,并注意防止绝缘操作杆被人体或设备短接。

Hand part (8) the operator shall not be crossed with ring, to maintain the effective length of the insulation, and pay attention to prevent nipple insulation lever by the human body or equipment.

(9)为防止因受潮而产生较大的泄漏电流,危及操作人员的安全,在使用绝缘操作杆拉合隔离开关或经传动机构拉合隔离开关和断路器时,均应戴绝缘手套。

(9) to prevent leakage current due to be affected with damp be affected with damp is bigger, endanger the safety of the operators in the use of insulating lever pull and isolating switch or by the transmission mechanism and isolating switch and circuit breaker, insulating gloves should be worn.

(10)雨天在户外操作电气设备时,绝缘操作杆的绝缘部分应有防雨罩,罩的上口应与绝缘部分紧密结合,无渗漏现象,以便阻断流下的雨水,使其不致形成连续的水流柱而大大降低湿闪电压。

(10) rainy day in the outdoor operating electrical equipment, insulation lever should be the insulation cover, cover the top should be closely integrated with insulation parts, no leakage phenomenon, in order to block the flow of rainwater, make its not form a continuous flow of water column pressure and reduce wet lightning.

(11)雨天使用绝缘操作杆操作室外高压设备时,应穿绝缘靴。

(11) on rainy days when using insulation lever operation outdoor high voltage equipment, shall wear insulating boots.

(12)绝缘操作杆应每年进行一次工频耐压试验,不合格者严禁使用。

(12) insulation lever should be a year for a power frequency withstand voltage test, are not eligible is strictly prohibited.